VFD and Controller Settings Does It Matter ??? And Kevin Loves His Neighbors Episode - 522 Video
37 minutes Posted Jun 1, 2026 at 4:59 am.
0:00
37:48
Download MP3
Show notes

VFD and Controller Settings Does It Matter ??? And Kevin Loves His Neighbors Episode - 522


Stop the VFD Hunt: Fixing 0–10V Scaling, Ramps, and Skip Frequencies (Advanced Refrigeration Podcast)


Brett Wetzel and Kevin Compass kick off the Advanced Refrigeration Podcast with early-morning chaos, then dive into a common rack problem: VFD and controller settings that don’t match, causing suction oscillation and valve hunting. Using an E3/E2-style controller and a Danfoss drive example, they explain correcting the 0–10V analog output scaling so the drive responds immediately (often setting the low end to about 5V and matching minimum reference), aligning minimum/maximum references and speed limits (e.g., typical low-speed limits around 28–30 Hz and high limits around 60 Hz), and avoiding overly aggressive ramp rates that worsen overshoot. They also discuss using skip/bypass frequencies to eliminate resonance that shakes racks, breaks clamps, and damages piping, noting common troublesome ranges seen on certain compressors.